Noise Criteria (NC)
and Noise Rating (NR)
methods used to describe steady background sound in rooms by
comparing an octave-band spectrum against a family of reference curves.
ON THIS PAGE
They serve a similar purpose but come from different traditions. NC is widely used in North American building and HVAC acoustics, while NR is more common in European and international specifications. The two methods are related, but they are not interchangeable.
Both exist because a room’s acoustic acceptability depends on more than its overall A-weighted sound level.
A mechanical system may produce a seemingly acceptable broadband dBA value while still containing excessive low-frequency rumble, mid-frequency roar or high-frequency hiss. Octave-band ratings retain that spectral information and help identify where the problem is occurring.
Why Room Noise Needs a Spectral Rating
A single broadband sound level compresses a complex spectrum into one number.
That is useful for many purposes, but it can hide frequency-specific problems.
A-weighting, for example, substantially reduces the contribution of low-frequency sound. A fan, pump or duct system with strong energy at 63 or 125 Hz may therefore appear relatively modest when expressed only as dBA, even though occupants perceive a distinct rumble.
NC and NR ratings address this by comparing the measured sound level in individual octave bands against a defined family of curves.
Because the rating depends on the spectrum, NC and NR cannot be determined from a broadband dBA value alone.
A sound level meter or analyzer needs the appropriate 1/1-octave-d data to perform the assessment.
The NC Curve Family
Noise Criteria curves were originally developed in the United States to provide designers with a practical method for evaluating steady background noise from building services such as heating, ventilation and air-conditioning systems.
The standard NC curve family uses octave-band sound-pressure levels from 63 Hz through 8 kHz.
The rating is determined by comparing the measured spectrum against the NC curve family. The resulting NC value is the lowest-numbered curve that is not exceeded by the measured octave-band spectrum.
In practical terms, the rating is controlled by the band—or bands—where the measured spectrum comes closest to the governing curve.
For example, if a room’s octave-band spectrum is controlled by the NC-45 curve at 125 Hz while remaining below lower-numbered curves elsewhere, the overall room rating is NC 45, and the 125 Hz band identifies the part of the spectrum most responsible for that result.
That information is valuable because it tells the acoustic engineer or mechanical designer where corrective action is likely to have the greatest effect.
Current ASHRAE guidance continues to use NC as one of the principal methods for describing HVAC-related background sound and recommends reporting the octave-band spectrum and the frequency that controls the rating, rather than reporting the NC number alone.
The NR Curve Family
Noise Rating curves serve a similar purpose in international and European building-acoustics practice.
Like NC, NR evaluates an octave-band spectrum against a family of reference curves and produces a single-number rating based on the limiting part of that spectrum.
The precise frequency range used can depend on the implementation.
For example, SVANTEK’s SV 307A supports NR evaluation using its octave-band analysis capability. Its current manual confirms that the instrument supports real-time 1/1- and 1/3-octave analysis as an optional measurement function.
The important practical point is not that one rating system is universally stricter than the other.
It is that NC and NR use different curve families and should not be substituted for one another.
If a project specification calls for NC but an equipment datasheet provides only an NR rating, the correct approach is to obtain the underlying octave-band spectrum and evaluate it using the required NC method.
A single NR number cannot reliably be converted into an NC number without the spectrum behind it.
NC or NR: Which One Should a Project Use?
The governing project specification should determine the method.
| Noise Criteria (NC) | Noise Rating (NR) | |
|---|---|---|
| Historical origin | United States / North American building acoustics | International / European building acoustics |
| Typical octave-band evaluation | 63 Hz–8 kHz | Depends on the applicable implementation |
| Common use | HVAC design, building acoustics and commissioning in North America | European and international building specifications |
| Referenced in | ASHRAE guidance and U.S. room-noise practice | International and European acoustic practice |
| Interchangeable? | No | No |
For U.S. projects, NC is commonly encountered in mechanical design, commissioning and architectural acoustics, while NR is more likely to appear in equipment specifications or projects using international design standards.
Neither should be selected simply because it is familiar.
The project specification, owner requirements and applicable acoustic standard should determine which method is used.
Typical ASHRAE Design Guidance
ASHRAE publishes recommended background-sound design criteria for various occupied spaces.
These values are intended primarily as design guidance for building mechanical systems, not universal legal limits on total sound in every room.
Representative values include:
| Space | Recommended NC / RC | Approx. dBA | Approx. dBC |
|---|---|---|---|
| Drama theaters / concert halls | 20 | 25 | 50 |
| Teleconference rooms | 25 | 30 | 55 |
| Music teaching studios | 25 | 30 | 55 |
| Residences / living areas | 30 | 35 | 60 |
| Executive and private offices | 30 | 35 | 60 |
| Conference rooms | 30 | 35 | 60 |
| Classrooms | 30 | 35 | 60 |
| Hospital patient rooms | 30 | 35 | 60 |
| Open-plan offices | 40 | 45 | 65 |
| Gymnasiums | 45 | 50 | 70 |
These values are general design guidelines. Actual project criteria may vary according to room use, acoustic expectations, equipment type and owner requirements. ASHRAE notes that appropriate design criteria may vary around the recommended values depending on the specific application.
A useful lesson from the table is that a room can satisfy its overall dBA target while still having an undesirable spectral balance.
For example, an unusually large difference between A- and C-weighted measurements can indicate that low-frequency energy deserves further investigation, although the octave-band spectrum is ultimately more informative than a broadband comparison alone.
A Note on Classroom Criteria
Classrooms are a good example of why design guidance and enforceable or standard-based criteria should not be confused.
ANSI/ASA S12.60 establishes acoustic criteria specifically for learning spaces. Published Acoustical Society of America guidance identifies a one-hour average background limit of 35 dBA for core learning spaces up to 20,000 ft³, with different criteria applying to larger and ancillary spaces.
That requirement addresses the overall acoustic environment of the learning space, not simply HVAC design noise.
Beyond NC: RC Mark II, NCB and RNC
NC remains widely used because it is straightforward.
Its limitation is that the final rating is largely controlled by whichever octave band approaches the curve most closely. Two rooms can therefore receive the same NC rating while sounding quite different.
Other methods have been developed to provide more information about the spectral character of room noise.
Room Criteria Mark II
The Room Criteria Mark II (RC Mark II) method provides both a numerical rating and an assessment of spectral balance.
Current ASHRAE guidance describes RC Mark II using quality descriptors that help identify the character of the background sound. These include:
| Descriptor | General interpretation |
|---|---|
| N | Neutral spectrum |
| LF | Low-frequency dominated / rumble |
| MF | Mid-frequency dominated / roar |
| HF | High-frequency dominated / hiss |
The method can also identify low-frequency conditions associated with vibration or perceptible building response.
This makes RC Mark II more diagnostic than a basic NC number alone.
For example, two rooms may have similar overall ratings, but one may have a balanced spectrum while another has a pronounced low-frequency component from fans, pumps or structure-borne mechanical equipment.
ASHRAE’s current guidance treats RC Mark II as the preferred revised form of the RC approach when that methodology is used.
Balanced Noise Criteria
Balanced Noise Criteria (NCB) was developed to improve on the original NC method by providing additional consideration of spectral balance and low-frequency sound.
It remains useful background knowledge when reviewing older specifications, design documents and room-acoustics literature.
However, it should not automatically be described as a current ANSI/ASA S12.2 method without checking the applicable edition of the standard.
Room Noise Criteria
Room Noise Criteria (RNC) was developed for situations where low-frequency HVAC sound varies or surges over time and may not be adequately characterized by steadier rating methods.
ASHRAE continues to discuss RNC for reference but states that it has no formal position on its use.
If a specification calls for RNC, confirm the intended measurement and evaluation procedure rather than assuming it is interchangeable with NC or RC.
ANSI/ASA S12.2 Has Changed
This is an important update for anyone relying on older room-noise references.
The current edition is ASA/ANSI S12.2-2026, Criteria for Evaluating Room Noise.
It supersedes the previous 2019 edition.
The published scope of the 2026 standard identifies two principal methods for evaluating steady-state room noise from heating, ventilating and air-conditioning systems:
- A-weighted sound level, and
- Noise Criteria (NC) curves.
That means older descriptions suggesting that ANSI/ASA S12.2 currently serves as a framework tying together NC, RC, NCB and RNC should be treated cautiously.
Those methods are still relevant historically and technically, and some remain discussed in ASHRAE guidance, but the current standard should be checked directly whenever a project specification references ANSI/ASA S12.2.
Measuring NC and NR Correctly
Room-noise ratings depend on individual octave bands, so measurement procedure matters.
Start with the governing project specification or standard.
In general:
- Measure the room under the operating conditions the assessment is intended to represent;
- Use 1/1-octave-band analysis over the frequency range required by the rating method;
- Select microphone locations representative of the occupied area;
- Avoid relying on a single measurement point where room modes or localized mechanical noise could distort the result;
- Use measurement durations long enough to capture relevant system cycling or variation;
- Follow the calibration or field-check procedure required by the applicable method; and
- Report the octave-band spectrum alongside the final NC, NR or other room-noise rating.
A result reported only as “NC 38”, for example, tells the reader much less than a result that also includes the octave-band spectrum and identifies which frequency band controlled the rating.
The spectrum allows another reviewer to understand the acoustic problem, verify the rating and evaluate possible corrective measures.
What Instrument Class Is Required?
Do not assume that every NC or NR measurement automatically requires a Class 1 sound level meter.
The required instrument class should come from the governing standard, project specification or measurement objective.
Class 1 instruments offer tighter performance limits and may be preferred for professional measurements where higher accuracy, broader environmental performance or additional technical scrutiny is expected.
Class 2 instruments can also be appropriate where the applicable method permits them.
For screening, troubleshooting and many building-acoustics measurements, the most important requirements are often:
- appropriate instrument performance;
- accurate 1/1-octave-band analysis;
- suitable calibration;
- representative measurement positions; and
- correct application of the required rating method.
For more on this distinction, see Class 1 vs Class 2 Sound Level Meters.
Instruments for NC and NR Measurements
For attended room-acoustics measurements, a handheld analyzer with real-time octave-band capability is typically the most practical tool.
The SVANTEK SV 971A, for example, can be used for professional attended sound measurements and octave-band analysis.
NC and NR ratings are evaluated from octave-band data, not from a single broadband reading.
For longer-term or unattended measurements, the SVANTEK SV 307A supports real-time 1/1- and 1/3-octave analysis as an optional function, along with remote monitoring and data logging. The current approved manual also documents configurable octave analysis and logged spectrum data.
Longer-term monitoring can be useful where room noise changes with:
- HVAC operating mode;
- nighttime setback;
- outdoor conditions; or
- equipment staging;
- occupancy schedule;
- intermittent plant operation.
In those cases, a sequence of octave-band spectra across the complete operating cycle may provide substantially more useful information than a single spot reading.
The Practical Takeaway
NC and NR are useful because they describe where the acoustic energy sits in the spectrum, not simply how loud the room is overall.
For North American projects, NC remains one of the most commonly used room-noise rating methods, particularly in HVAC design and commissioning.
NR continues to appear frequently in international and European specifications.
Neither should be treated as interchangeable, and neither should be interpreted without the octave-band spectrum that produced it.
When greater diagnostic detail is needed, methods such as RC Mark II can help describe whether the sound is spectrally neutral or dominated by low-, mid- or high-frequency energy.
The most important rule is simple:
Use the rating method required by the project, measure the full spectrum correctly, and report enough information for someone else to understand and verify the result.
For more on octave-band analysis, background sound, sound frequency and instrument selection, visit the Specto Noise Academy.